1Service
Set Point at Maximum Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as SETPOINT, the set point represented by the Volts at Maximum parameter (H4) is set by parameter H7. The minimum value is the Set Point at Minimum Volts setting H6 and the maximum is 190°F (88°C). The default value is 180°F (82°C).
On Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Thermostat Input is set to INACTIVE, parameter H8 determines the 0 - 10V BMS input voltage at which the water heater is enabled. The minimum value is 0.5V and the maximum is 10.0V. The default value is 2.0V.
Off Differential Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Thermostat Input is set to INACTIVE, parameter H9 determines how far below the On Volts setting H8 the 0 - 10V BMS input voltage must be in order to disable the water heater. The minimum value is 0.2V and the maximum is the On Volts setting H8. The default value is 1.0V.
I: Service Notification
Service Notification in Months
When the water heater control determines that a scheduled service is due based on days of installation, the water heater display will alternate the standard water heater display text with the message SERVICE DUE every 5 seconds. This parameter is adjustable by the installer by accessing parameter I1. The time range for this parameter is 0 months to 36 months. The default time is 0 months.
This feature has been disabled by the manufacturer. To enable this feature change parameter I1 to the desired time range.
Service Notification Running Time
When the water heater control determines that a scheduled service is due based on the hours of actual operation, the water heater display will turn yellow and a new status screen will appear informing the installer that maintenance is required. This parameter is adjustable by the installer by accessing parameter I2. The time range for this parameter is 0 hours to 100,000 hours. The default time is 8,760 hours.
Service Manual
Service Notification Cycles
When the water heater control determines that a scheduled service is due based on the number of water heater cycles, the water heater display will alternate the standard water heater display text with the message SERVICE DUE every 5 seconds. This parameter is adjustable by the installer by accessing parameter I3. The range for this parameter is 0 cycles to 100,000 cycles. The default is 50,000 cycles.
Reset Maintenance Reminder
Once servicing has been completed, the service notification counter should be reset. This parameter can be reset by the installer by accessing parameter I4. Once accessed, press the RESET key to reset the service notification counter.
Installer Name and Phone Number
NOTICE | Please note that the brackets ([]) denote | |
screen status. | ||
| ||
|
When a Maintenance Reminder timer or counter has expired, a Maintenance Reminder screen will appear on the display. By programming the installer’s name and phone number, this information will appear on the Maintenance Reminder Screen at that time. This can be programmed by accessing parameter I5. When selected, another menu will appear with PHONE and NAME.
1.Rotate the NAVIGATION dial to point to the name/phone number to program and press the NAVIGATION dial. The screen will now display the selected item (either PHONE or NAME).
2.Press the NAVIGATION dial again. A cursor will appear at the bottom of the screen. By rotating the NAVIGATION dial, various numbers and characters will appear. When the desired number/character is found, press the NAVIGATION dial. The cursor will move to the next position.
3.Repeat this procedure until the entire message is
entered. If you make a mistake and wish to back up one character, select the back arrow (←) character and press the NAVIGATION dial.
4.When finished, press the RIGHT SELECT [SAVE] key to return to the previous menu.