Service Manual
3Troubleshooting (continued)
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT | DESCRIPTION | CORRECTIVE ACTION | ||||
|
|
| ||||
Flame Sequence |
| • Check supply voltage for proper polarity. | ||||
|
|
|
|
| ||
(will require a manual |
| • Check external wiring for voltage feedback. | ||||
reset once the condition |
| |||||
The flame detector circuit is seeing a flame |
|
|
|
| ||
has been corrected. Press | • Check the flame rod and make sure it is clean. | |||||
the RESET button on the | signal while no flame is present. | • Check the internal wiring for bad connections. | ||||
SMART SYSTEM display |
| |||||
|
|
|
|
| ||
to reset.) |
| • Replace main control board. | ||||
|
| |||||
|
|
| ||||
|
| • Verify that the system is full of water and that all air | ||||
|
| has been properly purged from the system. | ||||
|
| • Verify that the water heater is piped properly into the | ||||
|
| heating system. Refer to Section 6 - Hydronic Piping | ||||
|
| of the Armor Installation and Operation Manual | ||||
|
| for the proper piping methods for the Armor water | ||||
|
| heater. | ||||
|
| • Check 120 vac to water heater pump motor on a call | ||||
|
| for heat. If voltage is not present, check wiring back | ||||
|
| to the main control board. | ||||
|
| • Replace the main control board if necessary. | ||||
Auto Reset | The outlet water temperature has exceeded | • If 120 vac is present on a call for heat and the water | ||||
the setting of the automatic reset high limit. | heater pump is not operating, replace the pump. | |||||
High Limit |
|
|
|
| ||
| • If the system pump is a variable speed pump, ensure | |||||
|
| |||||
|
| that the system flow is not less than the water heater | ||||
|
| flow. | ||||
|
| • If operating on something other than an outlet sensor, | ||||
|
| check temperature setting of the main control board. | ||||
|
| • If the manual reset high limit has tripped, check | ||||
|
| setting of the device. | ||||
|
| • Check resistance of water sensors and compare to | ||||
|
| Table B on page 26 of this manual. Replace | ||||
|
| sensor if necessary. | ||||
|
| • Replace high limit. | ||||
|
| • Verify that the system is full of water and that all air | ||||
|
| has been properly purged from the system. | ||||
|
| • Verify that the water heater is piped properly into the | ||||
|
| heating system. Refer to Section 6 - System Piping | ||||
|
| of the Armor Water Heater Installation and Operation | ||||
Manual Reset |
| Manual for the proper piping methods for the Armor | ||||
| water heater. | |||||
High Limit |
| |||||
| • Check 120 VAC to water heater pump motor on a call | |||||
(will require a manual |
| |||||
| for heat. If voltage is not present, check wiring back | |||||
reset once the condition | The outlet water temperature has exceeded | |||||
to the main control board. | ||||||
has been corrected. Press | the fixed setting of the manual reset high | |||||
|
|
|
| |||
the RESET button on the | limit. | • Replace the main control board if necessary. | ||||
SMART SYSTEM display |
| • If 120 VAC is present on a call for heat and the water | ||||
to reset.) |
| heater pump is not operating, replace the pump. | ||||
|
| • If the manual reset high limit has tripped, check | ||||
|
| setting of the device. | ||||
|
| • Check resistance of water sensors and compare to | ||||
|
| Table 3C on page 26 of this manual. Replace sensor | ||||
|
| if necessary. | ||||
|
| • Replace high limit. | ||||
|
|
|
| 31 |
| |
|
|
|
| |||
|
|
|
|