Lochinvar 151 - 801 Outlet Temp High, Rem Ctrl Flt, Service Blk, 3Troubleshooting, Fault

Models: 151 - 801

1 40
Download 40 pages 22.57 Kb
Page 34
Image 34
Outlet Temp High

Service Manual

3Troubleshooting

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

• Verify that the water heater is piped properly into the

 

 

heating system. Refer to Section 6 - System Piping

 

 

of the Armor Water Heater Installation and Operation

 

 

Manual for the proper piping methods for the Armor

Outlet Temp High

 

water heater.

Outlet water temperature has exceeded the

• Check for 120 VAC to the water heater pump motor on

 

maximum outlet water temperature.

a call for heat. If voltage is not present, check wiring

 

 

 

 

back to the main control board. Replace the main

 

 

control board if necessary.

 

 

• If 120 VAC is present on a call for heat and the water

 

 

heater pump is not operating, replace the pump.

 

 

• Replace the main control board.

 

 

 

 

External control is cycling too often.

• Check set point of the external control.

 

 

Rem Ctrl Flt

 

• Check the wiring between the external control and the

 

unit.

 

 

 

 

• Replace the control.

 

 

 

 

 

• Establish a heating load to remove the heat from the

 

 

water heater loop.

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

• Verify that the water heater is piped properly into the

 

 

heating system. Refer to Section 6 - System Piping

 

 

of the Armor Water Heater Installation and Operation

 

 

Manual for the proper piping methods for the Armor

 

 

water heater.

Service Blk

While the unit is in Service Mode, the outlet

• Check 120 VAC to the water heater pump motor on a

 

temperature has exceeded 185°F.

call for heat. If voltage is not present, check the wiring

 

 

 

 

back to the main control board. Replace the main

 

 

control board if necessary.

 

 

• If 120 VAC is present on a call for heat and the water

 

 

heater pump is not operating, replace the pump.

 

 

• Verify that the water heater pump is set to the proper

 

 

speed or that the water heater pump is the proper

 

 

size. Reference Section 6 - System Piping of the

 

 

Armor Water Heater Installation and Operation

 

 

Manual for water heater pump specifications.

 

 

 

Rem Ctrl Flt 34 Service Blk

Page 34
Image 34
Lochinvar 151 - 801 Outlet Temp High, Rem Ctrl Flt, Service Blk, 3Troubleshooting, Fault, Description, Corrective Action