Service Manual
3Troubleshooting (continued)
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT | DESCRIPTION | CORRECTIVE ACTION |
| |||
|
|
|
| |||
| The main control board has received a call | • The control board will release the call for heat after a |
| |||
| for heat too quickly after the previous call for | set time period. |
| |||
heat has ended. |
|
|
|
|
| |
| • The control board will release the call for heat if the |
| ||||
|
|
| ||||
|
| outlet temperature drops too quickly. |
| |||
|
|
|
| |||
| The unit has failed to prove main burner | • Inspect spark electrode and associated wiring for |
| |||
| ignition after four (4) attempts. | damage and connection. Reference page 22 of this |
| |||
|
| manual for removal and cleaning procedures. |
| |||
| Exception: Models 501 - 801 will lock out | Replace if necessary. |
| |||
| after one retry for ignition. It will require a | • Check for proper electrical grounding of the unit. |
| |||
| manual reset before attempting to fire again. |
| ||||
|
| • Check incoming supply gas pressure. Natural gas |
| |||
|
| pressures should be between 4 - 14 inches w.c. and |
| |||
|
| LP gas pressures should be between 8 - 14 inches w.c. |
| |||
|
| Refer to Section 7 - Gas Connections of the Armor |
| |||
|
| Water Heater Installation and Operation Manual for |
| |||
|
| detailed information concerning the gas supply. |
| |||
|
| • Verify that the plastic hose from the gas valve to the air |
| |||
|
| inlet is connected and is not damaged. |
| |||
|
| • Verify that the vent/air intake pipes are correctly |
| |||
|
| installed and that there are no obstructions. |
| |||
|
| • Check for 24 VAC to the gas valve at the |
| |||
Flame Fail Ign |
| connection on the side of the main control board during |
| |||
| the ignition attempt. If no voltage is present, replace |
| ||||
(will require a manual |
| the main control board. |
| |||
reset once the condition |
| • If 24 VAC is present at the main control board, check |
| |||
has been corrected. |
|
| ||||
| the wiring between the main control board and the gas |
| ||||
Press the RESET button |
|
| ||||
| valve. Replace the wiring if necessary. Do not |
| ||||
on the SMART SYSTEM |
|
| ||||
| disconnect the wiring from the gas valve and attempt to |
| ||||
display to reset.) |
|
| ||||
| measure voltage at that point. The main control board |
| ||||
|
|
| ||||
|
| can detect if the gas valve is not connected and will |
| |||
|
| display the GV / Relay Fail fault. |
| |||
|
| • If 24 VAC is present, check the outlet of the valve to |
| |||
|
| ensure the valve is flowing gas. With a manometer |
| |||
|
| connected to the outlet tap of the gas valve, when the |
| |||
|
| unit is in the prepurge period, there should be a |
| |||
|
| negative pressure present. When the valve is |
| |||
|
| energized a change in pressure should occur. If the |
| |||
|
| pressure change does not occur, the gas valve is not |
| |||
|
| opening. Replace the gas valve. |
| |||
|
| • Inspect flame sensor and associated wiring. |
| |||
|
| Reference page 22 of this manual for removal and |
| |||
|
| cleaning procedures. Replace if necessary. |
| |||
|
| • Inspect the burner. Reference page 22 of this manual |
| |||
|
| for removal and cleaning procedures. Replace if |
| |||
|
| necessary. |
| |||
|
| • Replace the main control board. |
| |||
|
|
|
|
|
|
|
|
|
|