Commercial Pool Heaters
INSTALLATION Continued
MODEL NO. | BYPASS PIPE SIZE |
| |
CP (N,L) 501 - 751 | 2” MINIMUM |
| |
CP (N,L) 991 - 2071 | 2 1/2” MINIMUM | FACTORY POOL | |
RETURN SENSOR | |||
|
| ||
|
| LOCATION | |
|
| AUTOMATIC | |
|
| BYPASS VALVE | |
|
| PVC (SEE TABLE) |
FROM FILTER
COPPER OR CPVC (SEE TABLE)
RECOMMENDED
ISOLATION VALVE
VALVE
COPPER OR CPVC
(SEE TABLE)
| 110° LIMIT | 3' |
| MINIMUM | |
|
| |
TO POOL |
| ALTERNATE POOL |
|
| RETURN SENSOR |
|
| LOCATION |
Figure 36 - Heaters are within 15 feet Perpendicular of Pool Piping
MODEL NO. | BYPASS PIPE SIZE |
|
|
CP (N,L) 501 - 751 | 2” MINIMUM |
|
|
CP (N,L) 991 - 2071 | 2 1/2” MINIMUM |
|
|
|
| ALTERNATE POOL | FROM FILTER |
|
| RETURN SENSOR | |
|
|
| |
|
| LOCATION |
|
| 3' |
| 4" PVC |
| MINIMUM |
|
|
|
| FLOWMETER |
|
110° LIMIT |
|
| |
|
| 3" PVC |
|
| FLOWMETER |
|
|
TO POOL | 3" PVC |
|
|
|
|
| |
|
|
| RECOMMENDED |
|
|
| ISOLATION VALVE |
|
|
| FACTORY POOL |
|
|
| RETURN SENSOR |
|
|
| LOCATION |
|
|
| AUTOMATIC |
|
|
| BYPASS VALVE |
|
| COPPER OR CPVC | |
|
| (SEE TABLE) |
|
Figure 37 - Heaters are Beyond 15 feet of Pool Piping