TABLE-P

Installation and Service Manual

Refer to Circulating Pump on page 46 for information relating to pump wiring.

TABLE-P

AMP Draw Data

Btu/Hr

Controls

Fans

Pump

Approximate

Input

 

 

 

Total Amps

500,000

3.6

2.7

5.0

11.3

 

 

 

 

 

650,000

5.4

3.4

5.0

13.8

 

 

 

 

 

750,000

5.4

3.4

5.0

13.8

 

 

 

 

 

990,000

7.3

3.2

7.4

17.9

 

 

 

 

 

1,260,000

7.3

3.2

7.4

17.9

 

 

 

 

 

1,440,000

7.3

6.7

7.4

21.4

 

 

 

 

 

1,800,000

7.3

6.7

8.8

22.8

 

 

 

 

 

2,070,000

7.3

6.7

8.8

22.8

 

 

 

 

 

Pipe Size Requirements

The pipe sizing chart provides the minimum pipe size for common manifold piping to ensure adequate flow.

TABLE-Q

Pipe Sizing Chart

500,000 - 750,000 Btu/hr Models

Common Pipe

Number of Units

Size (Min.)

1

2"

 

 

2

3"

 

 

3

3 1/2"

 

 

4

4"

 

 

5

5"

 

 

6

5"

 

 

990,000 - 2,070,000 Btu/hr Models

Common Pipe

Number of Units

Size (Min.)

1

2 1/2"

 

 

2

4"

 

 

3

4"

 

 

4

5"

 

 

5

6"

 

 

6

6"

 

 