Commercial Pool Heaters

INSTALLATION Continued

Gas Manifold Pressure Adjustment

IMPORTANT: The gas valves are referenced to the fan pressurized chamber by a hose connected from the vent of the gas valve regulator to the chamber pressure tap located on the front inside portion of the jacket. Reference the drawings in this section for component and connection points for pressure measurement. The procedure for connecting a manometer or magnahelic must be followed to obtain actual net manifold pressure for normal operation. A manometer or magnahelic gauge legible in 0.1" increments up to 10 inches w.c. is required to check and adjust the manifold pressure. The regulator cover screw on the gas valve must be in place and tight at all times for the pool heater to operate properly.

1.Remove the thumbscrew that fastens the control panel access door and pull out the control panel.

2.Turn the power switch located in the lower left corner behind the control panel access door to the “O” or “OFF” position.

3.Remove the top front jacket access panels to access the gas valves.

4.Locate the reference hose on the second gas valve which goes from the vent fitting on the gas valve to a barbed fitting on the deck of the pool heater (see Figure 31).

5.Remove the flexible cap from the barbed fitting on the “tee” located in this line and hook one side of the manometer, or (-) side of a magnahelic gauge, to this “tee”. Retain this cap for future use.

6.Remove the 1/8" hex plug from the manifold pressure tap on the gas valve (see Figure 31). Retain plug for future use.

7.Install a fitting in this tap that is suitable for connection of a hose to a manometer, or (+) side of a magnahelic gauge (see Figure 31).

8.Turn the power switch to the “I” or “ON” position.

9.Push the reset button(s) for the ignition control(s), if necessary.

10.Set the temperature control to call for heat (see Programming Temperature Control, page 41).

11.Once the pool heater is firing the manometer/magnahelic will reflect the Manifold Gas Pressure. Compare this reading to the respective value in TABLE-L, page 31 for Natural or Propane Gas.

12.If adjustment is necessary, remove the regulator cover screw on the gas valve.

Note: If the gas valve under adjustment is located on a manifold assembly monitored by an igniter, the pool heater may shut down and recycle when the regulator cover screw is removed. This is normal.

13.

Turn the regulator adjustment screw “clockwise” ; to raise the

 

regulator gas pressure. Turn the regulator adjustment screw

 

“counterclockwise”; to lower the regulator gas pressure.

14.

Replace the regulator cover screw and make sure it is tight for

 

proper operation.

15.

Read the value on the manometer/magnahelic and compare it

 

to the values in TABLE-L.

16.

Repeat this adjustment procedure for each gas valve as necessary

 

to adjust to the proper manifold gas pressure.

MANIFOLD

PRESSURE

4

 

3

 

2

 

1

 

0

 

1

CHAMBER

 

2

PRESSURE

3

4

MANOMETER

CAP

 

INLET

PRESSURE

REGULATOR

 

ADJUSTMENT

 

(UNDER CAP SCREW)

BARBED

 

FITTING

 

GAS

 

VALVE

 

CONTROL

 

KNOB

 

 

1/8" HEX

 

MANIFOLD

OUTLET

PRESSURE

TAP

 

17.

Remove hoses, replace and tighten plugs and caps when

 

complete.

18.

Replace top front upper jacket access panels and control panel

 

door in reverse order.

19.

If proper ignition and burner operation is not achieved after

 

checking gas supply pressure, see Cleaning and Maintenance,

 

page 49 for Combustion Air Fan Adjustment. Follow the

 

procedure to adjust the combustion air fans as necessary.

Figure 31 – Measuring Net Manifold Gas Pressure

30

Page 30
Image 30
Lochinvar F0600187510 service manual Gas Manifold Pressure Adjustment, To adjust to the proper manifold gas pressure

F0600187510 specifications

The Lochinvar F0600187510 stands out as a premium combination boiler that caters to the heating and hot water needs of residential properties. Known for its energy efficiency and advanced technology, this model is ideal for homeowners seeking both comfort and cost savings.

One of the primary features of the Lochinvar F0600187510 is its exceptional energy efficiency. With an impressive AFUE (Annual Fuel Utilization Efficiency) rating, this boiler redefines performance standards, effectively converting a high percentage of the energy it consumes into usable heat. This not only helps in reducing energy bills but also contributes to lower carbon emissions, making it an environmentally responsible choice.

The F0600187510 is equipped with Lochinvar's advanced control system, which allows for precise temperature regulation. This system includes a user-friendly digital display, enabling homeowners to easily adjust settings for their specific heating and hot water requirements. The boiler also offers weather compensation features that optimize performance based on outdoor temperatures, ensuring maximum efficiency throughout the year.

In terms of hot water production, this model features a built-in indirect water heater design, which provides an abundant supply of domestic hot water on demand. This is ideal for households with high hot water usage, as the system can deliver multiple gallons per minute without interruption.

Moreover, the compact design of the Lochinvar F0600187510 allows for flexible installation options, making it suitable for various settings, including tight spaces. Its robust construction ensures durability and reliability, giving homeowners peace of mind regarding long-term performance.

Safety is another significant characteristic of this combination boiler. It comes with multiple built-in safety features, including flame detection, pressure sensors, and overheat protection, ensuring the system operates securely and efficiently.

Finally, the Lochinvar F0600187510 is backed by a solid warranty, providing homeowners with additional assurance of quality and support. Overall, this boiler represents a harmonious blend of innovative technology, efficiency, and reliability, making it a top choice for modern residential heating and hot water solutions.