Installation and Service Manual
13.Remove the manometer and related fitting from the “inlet” side of the gas valve, replace 1/8" hex plug in the gas valve and
tighten.
14. Turn on the gas supply at the manual valve, turn on L.P. gas at the tank if required.
15. Turn the power switch to the “ON” position.
16. Turn the gas valve knobs to the “ON” position.
17. Set the temperature control to call for heat.
WARNING: After completing any testing on the gas system, leak test all gas connections. Apply a soap/water solution to all gas connections while main burners are operating. Bubbles forming indicate a leak. Repair all leaks at once. Do not operate this pool heater with a leak in the gas train, valves or related piping.
Check burner performance by cycling the system while you observe burner response. Burners should ignite promptly. Flame pattern should be stable, see Burner Flames, page 47. Turn system off and
allow burners to cool, then cycle burners again to ensure proper | Figure 30 – Measuring Gas Supply Pressure at Combination | ||||||||||||||
| Gas Valve |
|
|
|
|
| |||||||||
ignition and flame characteristics. |
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| TABLE - K |
|
|
|
|
|
|
| |
|
|
|
| Multiple Unit Installations Gas Supply Pipe Sizing |
|
|
|
| |||||||
Nominal |
|
|
|
|
| Length of Pipe in Straight Feet |
|
|
|
| |||||
Iron Pipe |
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Size | 10 | 20 |
| 30 | 40 | 50 | 60 | 70 | 80 | 90 | 100 | 125 | 150 | 175 | 200 |
(Inches) |
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3/4" | 369 | 256 |
| 205 | 174 | 155 | 141 | 128 | 121 | 113 | 106 | 95 | 86 | 79 | 74 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1" | 697 | 477 |
| 384 | 328 | 292 | 267 | 246 | 256 | 210 | 200 | 179 | 164 | 149 | 138 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 1/4" | 1,400 | 974 |
| 789 | 677 | 595 | 543 | 502 | 472 | 441 | 410 | 369 | 333 | 308 | 287 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 1/2" | 2,150 | 1,500 |
| 1,210 | 1,020 | 923 | 830 | 769 | 707 | 666 | 636 | 564 | 513 | 472 | 441 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2" | 4,100 | 2,820 |
| 2,260 | 1,950 | 1,720 | 1,560 | 1,440 | 1,330 | 1,250 | 1,180 | 1,100 | 974 | 871 | 820 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2 1/2" | 6,460 | 4,460 |
| 3,610 | 3,100 | 2,720 | 2,460 | 2,310 | 2,100 | 2,000 | 1,900 | 1,700 | 1,540 | 1,400 | 1,300 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3" | 11,200 | 8.900 |
| 6,400 | 5,400 | 4,870 | 4,410 | 4,000 | 3,800 | 3,540 | 3,300 | 3,000 | 2,720 | 2,500 | 2,340 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
4" | 23,500 | 16,100 |
| 13,100 | 11,100 | 10,000 | 9,000 | 8,300 | 7,690 | 7,380 | 6,870 | 6,150 | 5,640 | 5,130 | 4,720 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Maximum capacity of pipe in thousands of BTU’s per hour for gas pressures of 14 Inches Water Column (0.5 PSIG) or less and a total system pressure drop of 0.5 Inch Water Column (Based on NAT GAS, 1025 BTU’s per Cubic Foot of Gas and 0.60 Specific Gravity).
29