1 4 | Installation (For Qualified Installers Only) |
Installation Example: Interior Vertical Installation
3” | 2” |
Minimum | Minimum |
| |
| “Tee” |
| Outside |
Type "L" Vent | Air |
| (optional) |
| 9” Minimum |
Floor Protection | 6” Minimum |
|
Vertical Cap
24” Minimum
Storm Collar
Roof Flashing
Insulation must maintain 3” clearance.
Vent must |
maintain 3” |
clearance to |
combustibles. |
3” Min.
Ceiling Support / Fire Stop Spacer
“L” Vent
.RTV °F 500Silicone
Seal each vent section (including adapters, elbows, etc...) by injecting a liberal amount of 500° F. RTV silicone into the gap between sections.
2” Min.
Floor Protection
Outside air may be drawn from a ventilated crawl space.
Travis Industries | 4050418 | 1 0 0 - 0 1 1 5 6 |