Introduction 1

Battery Times for the UPS and BIM

During a power failure, the UPS battery supplies power to your equipment, providing time to complete computing activities prior to UPS shutdown￿ The duration of this time period is directly related to the UPS battery configuration￿ By adding battery modules, you can customize the UPS to provide enough battery time for normal processing activities￿

Load (VA)

 

Average Battery Time (in Minutes)

Load (W)

 

 

 

at .7 PF*

1 Module

2 Modules

3 Modules

 

 

 

 

 

 

 

 

600

420

36.8

88

146

 

 

 

 

 

800

560

27.6

66

110

 

 

 

 

 

1200

840

18.4

44

73

 

 

 

 

 

1600

1120

13.7

33

54

 

 

 

 

 

2000

1400

10.7

26

42

 

 

 

 

 

2500

1750

8.3

20

33

 

 

 

 

 

3000

2100

6.5

16

27

 

 

 

 

 

*Typical Power Factor ￿PF￿

Battery Times for the UPS with BDM

 

 

Average Battery Time (in Minutes)

Load (VA)

Load (W)

 

 

 

1 Module

2 Modules

3 Modules

 

 

 

 

 

 

 

600

402

36.8

88

146

 

 

 

 

 

800

533

27.6

66

110

 

 

 

 

 

1200

800

18.4

44

73

 

 

 

 

 

1600

1067

13.7

33

54

 

 

 

 

 

2000

1333

10.7

26

42

 

 

 

 

 

2500

1667

8.3

20

33

 

 

 

 

 

3000

2000

6.5

16

27

 

 

 

 

 

iNOTE If using an EBC, refer to the EBC manual for approximate battery times.

Lucent Technologies Model 3000 UPS Operator￿s Manual ￿167+405+119 Issue 3￿

3

Page 13
Image 13
Lucent Technologies 3000 VA manual Battery Times for the UPS and BIM, Battery Times for the UPS with BDM