Installation 3

2If you are using the floor mounting plate, complete Steps A and B. This plate is required only for seismic applications, but can also be used to prevent rolling or tipping of the assembled rack.

AFor Seismic Installation

Prepare the floor by referring to the hole pattern shown below. The mounting plate has four 0.375 diameter floor mounting holes for earthquake bolts (not provided). Secure the plate to the floor.

WALL

11.0I minimum recommended for

cablingSeismic Mounting Holes

16.16I

Unit

Depth

3.0I

For Stability

10.0I

FRONT 3.5I

6.5I

12.5I

Unit

Width

The plate does not need to be mounted to the floor, but must be secured to the caster base to prevent the stack from rolling.

BSecure the caster base to the mounting plate using four of the 1/4.20￿x￿1/2 screws provided. See Figure￿3 or Figure￿4 for part locations.

3Stack the modules onto the caster base according to the stacking order shown in Figure￿3 or Figure￿4.

Make sure the first module nests on the base and each additional module nests on the preceding one.

If multiple Stacking Modules are used, the caster bases may be secured together on the side with two of the 1/4.20 x 1/2 screws provided.