3Installation

4Press the Output Off button until the alarm beeps. All indicators flash simultaneously.

5Press and hold the Output￿ On button until the alarm beeps again.

Two indicators, corresponding with the current setting, remain flashing. The output voltage is factory/configured for 230V.

OVERLOAD

I1

I2

I3

OUTPUT ON

240V

230V

220V

208V

Figure 12. Output Voltage Indicators

6Press the Output Off button to scroll through the output voltage options, top to bottom. Each time you press the button, the UPS beeps and the next two indicators flash.

i NOTE If you do not save a selection within two minutes, the setup automatically aborts and switches back to the original configuration.

7Press and hold the Output￿ On button until the alarm beeps to select and save the output voltage. Failure to release the button immediately after the beep will cause the UPS to abort the setup.

8Turn on the equipment that is connected to the UPS.

9Press and hold the Output￿ On button until you hear the UPS beep (approximately one second).

The ￿Indicator remains lit and the Output On Indicator turns on. The front panel displays the percentage of full load being applied to the UPS. The UPS is now in Normal Mode with the load online. See •Normal Mode" on page 38 for more information.