Installation 3

UPS with Bypass Module Startup

￿o start up the ￿￿￿:

￿￿ake sure the Bypass switch on the Bypass ￿odule rear panel is in the

￿￿￿￿A￿ position (see ￿igure￿5 on page 26 or ￿igure￿6 on page 27).

￿￿f your Bypass ￿odule is a hardwired unit, supply utility power.

￿￿f your Bypass ￿odule is a plug/receptacle unit, plug the input power cord into the utility input connector on the Bypass ￿odule rear panel.

￿lug the other end of the power cord into a grounded, three2wire, AC receptacle that has been wired in accordance with ￿￿C specifications or national wiring rules. (￿ee ￿igure￿11 for an example.)

Phase 1

 

 

 

200/208/220/230/240V

L

 

N

Phase 2/Neutral

 

 

G

(International)

 

Ground

Figure 11. L6#30 Receptacle

iNOTE Steps 4 through 7 are for changing the output voltage. The output voltage is factory&configured for 230V. If you do not need to change the output voltage, skip to Step￿8. Use the following table to select the correct output voltage according to your Bypass Module.

Bypass Module Model Number

UPS Voltage Selection*

 

 

604Hz BDM 208: 120/208

208

 

 

604Hz BDM 208: 120/240

208

 

 

604Hz BDM 208: 120

208

 

 

604Hz BDM 240: 120/240

Set to 220V for 110/220V BDM output

 

Set to 230V for 115/230V BDM output

 

Set to 240V for 120/240V BDM output

 

 

604Hz BDM 240: 120

Set to 220V for 110V BDM output

 

Set to 230V for 115V BDM output

 

Set to 240V for 120V BDM output

 

 

504Hz BIM 208 ￿Model 2500 only￿

208

 

 

504Hz BIM 220

220

 

 

504Hz BIM 230

230

 

 

504Hz BIM 240

240

 

 

*The UPS output voltage should be set according to local mains voltage.

Lucent Technologies Model 3000 UPS Operator￿s Manual ￿16744054119 Issue 3￿

33