Lucent Technologies 3000 VA manual 604Hz BDM 240

Models: 3000 VA

1 75
Download 75 pages 48.04 Kb
Page 53
Image 53

UPS Operation 4

Use the following procedure to reinstall the UPS and transfer the critical load from Maintenance Bypass (AC Line operation) to the UPS:

￿Reconnect the battery modules to the battery connector on the UPS rear panel.

￿Turn the circuit breaker on all battery modules to the ON ( ) position.

￿Plug the Y+cord of the Bypass Module into the power connectors on the UPS as shown in Figure￿18.

i NOTE Steps 4 through 7 are for changing the output voltage. The output voltage is factory(configured for 230V. If you do not need to change the UPS output voltage, skip to Step￿8. Use the following table to select the correct output voltage according to your Bypass Module.

Bypass Module

UPS Voltage Selection*

Model Number

 

 

 

604Hz BDM 208: 120/208

208

 

 

604Hz BDM 208: 120/240

208

 

 

604Hz BDM 208: 120

208

 

 

604Hz BDM 240: 120/240

Set to 220V for 110/220V BDM output

 

Set to 230V for 115/230V BDM output

 

Set to 240V for 120/240V BDM output

 

 

604Hz BDM 240: 120

Set to 220V for 110V BDM output

 

Set to 230V for 115V BDM output

 

Set to 240V for 120V BDM output

 

 

504Hz BIM 208 ￿Model 2500 only￿

208

 

 

504Hz BIM 220

220

 

 

504Hz BIM 230

230

 

 

504Hz BIM 240

240

*The UPS output voltage should be set according to local mains voltage.

4Press the Output Off button until the alarm beeps. All indicators flash simultaneously.

Lucent Technologies Model 3000 UPS Operator￿s Manual ￿16744054119 Issue 3￿

43

Page 53
Image 53
Lucent Technologies 3000 VA manual 604Hz BDM 240