3Installation

￿Place the conduit through the access hole on the junction box (see Figure￿10). Connect the exposed conduit wires to the corresponding compression terminals (see the following table). Tighten the compression terminals with a screwdriver.

￿Pivot the REPO receptacle guard out of the way, plug the REPO plug/receptacle UPS connector into the REPO receptacle on the UPS rear panel (see Figure￿5 on page 26 or Figure￿6 on page 27). Twist the connector in place.

 

 

Mounting Holes

Plug/Receptacle

 

 

 

 

 

 

 

 

 

 

UPS Connector

 

 

Access Hole

 

 

 

 

 

for Conduit

 

 

 

 

 

 

 

Three Foot Cord

 

 

 

Terminal Block

 

 

 

 

 

Figure 10. REPO Cord Junction Box

 

 

 

Power Cable Terminations

 

Tightening Torque

 

Wire Function

Terminal

Terminal Wire

Entrelec

Phoenix

 

 

Position

Size Rating*

 

Contact

REPO

L1

TB184

 

 

 

 

L2

TB185

12822 AWG

3.5 - 5.3 lb/in

5.6 - 6.8 lb/in

 

(480 mm2)

 

Ground

TB186

 

 

 

*Suggested wire size is #188AWG (0.75 mm2) 75_C copper wire minimum.

NOTE: The REPO function activates when L1 and L2 are shorted together.

32

Lucent Technologies Model 3000 UPS Operator's Manual (16784058119 Issue 3)