Maretron Symptom, Troubleshooting Procedure, FPM100 User’s Manual, Page, Revision

Models: FPM100

1 23
Download 23 pages 7.43 Kb
Page 18
Image 18
5 Troubleshooting

FPM100 User’s Manual

5 Troubleshooting

If you notice unexpected operation of the Maretron FPM100, follow the troubleshooting procedures in this section to remedy simple problems.

Symptom

No Pressure data visible on NMEA 2000® network.

Inaccurate pressure output

No Tank Level data visible on NMEA 2000® network.

Inaccurate tank level output

Zero pressure readings when pressurized

Troubleshooting Procedure

1.Ensure that the FPM100 is properly connected to the NMEA 2000® network.

2.Ensure that pressure transducers are properly connected to the FPM100.

3.Ensure that each channel that you wish to monitor is configured as “Pressure/Vacuum”and that instance numbers are configured correctly.

4.Ensure that the FPM100 has the appropriate NMEA 2000 PGNs enabled.

1.Ensure that the “Pressure at 4mA” and “Pressure at 20mA” configuration items are set to appropriate values for the pressure transducer.

2.Check that the vent tube from the pressure transducer (only present on some transducers) is not kinked or blocked.

3.Remove the pressure transducer from the tank opening and ensure that the pressure port on the transducer is not clogged.

1.If operating in the NMEA 2000® Mode, check the connection to the NMEA 2000® interface (see Section 2.5.1) and tighten if necessary.

2.Ensure that power is supplied to the NMEA 2000® network. Proper network power can be checked by measuring the voltage at an open tee between NET-S and NET-C. The voltage should be between 9 and 16 volts.

3.Ensure that both trunk line terminators are in place. Proper network termination can be checked by removing network power and measuring the resistance at an open tee between NET-L and NET-H signals. The resistance should read approximately 60 ohms (two 120 ohm terminators in parallel equals 60 ohms).

1.If operating with a rectangular tank, ensure that the tank depth is programmed properly (see Section Error! Reference source not found.).

2.If using custom calibration, re-calibrate the FPM100 (see Section 3.3.5.2).

3.Check that the vent tube from the pressure transducer is not kinked or blocked.

4.Remove the pressure transducer from the tank opening and ensure that the pressure port on the transducer is not clogged.

1.Ensure that the “Pressure at 4mA” and “Pressure at 20mA” configuration items are set to appropriate values for the pressure transducer.

2.Check the cable connection to the pressure transducer to see whether a wire has become loose, or the cable has been cut.

Page 14

Revision 1.3

Page 18
Image 18
Maretron user manual Symptom, Troubleshooting Procedure, FPM100 User’s Manual, Page, Revision