Maytag MDG17MN Vent System Length, Multiple Dryer Venting, Maximum Vent Length

Models: MDG17MN

1 40
Download 40 pages 31.36 Kb
Page 8
Image 8

Plan installation to use the fewest number of elbows and turns.

AB

Exhaust Air Flow

A.Good

B.Better

Allow as much room as possible when using elbows or making turns. Bend vent gradually to avoid kinking.

Vent outlet is located at the center of the bottom dryer back.

The vent can be routed up, down, left, right, behind the dryer, or straight out the back of the dryer.

Vent System Length

Maximum length of vent system depends upon the type of vent used, number of elbows, and type of exhaust hood.

Maximum Vent Length

102 mm (4") Diameter Exhaust Hoods

Rigid Metal Vent

Each vent should enter the main vent at an angle pointing in the direction of the airflow. Vents entering from the opposite side should be staggered to reduce the exhausted air from interfering with the other vents.

The maximum angle of each vent entering the main vent should be no more than 30°.

A

30° max.

air flow

 

 

B

 

 

 

 

 

 

A. Individual dryer vent

B. Main vent

Keep air openings free of dry cleaning fluid fumes. Fumes create acids which, when drawn through the dryer heating units, can damage dryers and loads being dried.

A clean-out cover should be located on the main vent for periodic cleaning of the vent system.

If an exhaust hood cannot be used:

B

A

C

D

No. of 90° turns

Box Hood and Louvered Style

Angled Hood Style

 

 

 

0

19.5 m (64 ft.)

17.7 m (58 ft.)

1

16.5 m (54 ft.)

14.6 m (48 ft.)

2

13.4 m (44 ft.)

11.6 m (38 ft.)

3

10.7 m (35 ft.)

8.8 m (29 ft.)

4

8.2 m (27 ft.)

6.4 m (21 ft.)

If dryer is installed in a confined area, such as a bedroom, bathroom, or closet, provision must be made for enough air for combustion and ventilation. (Check governing codes and ordinances.) See “Recessed Area and Closet Installation Instructions” in the “Location requirements” section.

Min. 300 mm (12") clearance above any accumulation of snow, ice, or debris such as leaves.

C

A.Exhaust hood or elbow

B.Wall

C.Main collector vent

D.Horizontal vent

E.180° sweep elbow

F.Vertical vent

G.Roof

 

E

 

610 mm (24") min.

 

above highest

F

point of building

 

G

A 102 mm (4") outlet hood is preferred. However,a 64 mm (212") outlet exhaust hood may be used. A 64 mm (212") outlet creates greater back pressure than other hood types. For permanent installation, a stationary vent system is required.

Multiple Dryer Venting

A main vent can be used for venting a group of dryers. Main vent should be sized to remove 5663 l/min (200 CFM) of air per dryer. Large-capacity lint screens of proper design may be used in the main vent if checked and cleaned frequently. The room where the dryers are located should have make-up air equal to or greater than the airflow of all the dryers in the room.

Back-draft Damper Kit, Part No. 3391910, is available from your dealer and should be installed in each dryer’s vent to prevent exhausted air from returning into the dryers and to keep the exhaust in balance within the main vent.

Unobstructed air openings are required.

The outside end of the main vent should have a sweep elbow directed downward. If the main vent travels vertically through the roof, rather than through the wall, install a 180° sweep elbow on the end of the vent at least 610 mm (2 ft.) above the highest part of the building. The opening in wall or roof shall have a diameter 13 mm (12") larger than the vent diameter. The vent should be centered in the opening.

Do not install screening or cap over the end of the vent.

8

Page 8
Image 8
Maytag MDG17MN Vent System Length, Multiple Dryer Venting, Maximum Vent Length, 102 mm 4 Diameter Exhaust Hoods