Mega Catch Mini Installation, Wall Strap To supply power to the exhaust blower, Elbow

Models: Mini

1 31
Download 31 pages 17.59 Kb
Page 16
Image 16
90° Elbow

Installation

TYPICAL THROUGH WALL WITH EXTERIOR BLOWER KIT INSTALLATION - HORIZONTAL TERMINATION:

90° Elbow

45°Elbow with Rodent 2ft (610mm) RiserPipe AdaptorExterior Blowerand Housing screen or stainless Electrical CableWall StrapManual backgroundManual backgroundManual background steel termination hood Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

2ft (610mm) Riser

Pipe Adaptor

Exterior Blower

and Housing

Electrical Cable

Figure 21: Through Wall Installation with Exterior Blower Kit.

NOTE:

Ensure that all interior vent connections are sealed by placing a small bead of high temperature silicone around each chimney connection.

Also ensure that all vertical vent sections are properly supported and that all clearances to combustibles are maintained in accordance with the vent manufacturer’s specifications.

Wall Strap

To supply power to the exhaust blower

Figure 22: Through Wall Installation with Exterior Blower Kit; Side View.

Install the amour coated electrical cable from the exhaust blower housing, through the wall thimble plate and attach to the pre drilled hole in the left hand rear hopper pillar. Hook up to wires from the exhaust blower wiring harness.

All electrical connections must be in accordance to local code requirements

16