3. Operation
Voltage-thresholds tab
Configurable function |
| Default setting | Options |
|
|
|
|
| |
Output voltage on battery power |
| 230 V | 200 V - 220 V - 240 V | |
|
|
|
| |
Upper threshold for transfer to battery power |
| 294 V | 271 to 294 V | |
|
|
|
|
|
| 265 V | 244 to 265 | V | |
|
|
|
|
|
| 184 V | 184 to 207 | V | |
|
|
|
|
|
Lower threshold for transfer to battery power |
| 160 V | 160 to 180 | V |
|
|
|
| |
Maximum |
| Disabled | Enabled (1) | |
|
|
|
|
|
(1) Lower threshold for transfer to battery power = 150 V |
|
|
|
Sensitivity tab
Configurable function | Default setting | Options |
|
|
|
UPS sensitivity level | Normal | High or low |
|
|
|
For more informations about these settings, refer to the Help function of the "UPS Driver" software.