1.3Receiving and Inspection Notes
Before accepting the shipment from the freight carrier, inspect the exterior surfaces of all shipping containers or packaging used, and the equipment, for damage that may have occurred during transit. If the shipping containers or equipment shows evidence of damage, note the damage on the receiving document (bill of lading) prior to signing for receipt of equipment.
ALL CLAIMS FOR SHIPPING DAMAGE MUST BE FILED DIRECTLY WITH THE CARRIER. Replacements for damaged components should be ordered through MGE UPS SYSTEMS.
Check by thorough inspection if any electrical connections have become loose because of vibration during shipment. Remove top and side panels (Not applicable on 225kVA and larger).
Check the nameplate to be sure that the voltage and frequency match the available power supply. Under no circumstance should the unit be connected to a power source which does not conform to the nameplate rating.
1.3.1Location and Storage
The unit has been completely inspected and extensively tested under various load conditions prior to shipment. Care to install it at a proper location will assure long trouble free operation. The unit is forced air cooled with the air intake at the bottom, front or sides and exhausts out at the top or rear. Therefore, it should be installed in a clean, dry place with enough clearance to allow a free flow of air.
Allow at least 4 inches of space between the unit and the wall or other equipment for portable units.
Allow enough space for maintenance as indicated on the cabinet outlines. See Section 2.0, Figures
1.4General Description
The
The basic design consists of a three phase triple shielded isolation transformer with seven separate voltage taps per phase. Output regulation is achieved by monitoring the input and automatically switching taps anytime the input line sags or surges. The use of a triple shielded isolation transformer provides superior common mode and trans- verse mode noise attenuation. Automatic switching occurs during current zero allowing noise free switches for both leading and lagging power factor loads that are connected to the
The
Any ‘ALERT” condition requires the main AC input breaker to be turned off in order to reset the “ALERT” light.
1 — 2 | Introduction - Description |