1.4.1Electrical and Performance Specifications
*Output | Maintained to within ± 3% of nominal. |
*Input | +10% to |
*Frequency | 60 Hertz ± 3 Hertz. |
Efficiency | 95% Minimum. |
Line Regulation | Output is ± 3% of nominal for input variations of +10% to |
Load Regulation | Output maintained within 3% from no load to full load. |
Response Time | 1/2 Cycle. |
Correction Time | Output will correct in one step to within ±3% of nominal in 1.5 cycles or less. |
Harmonic Distortion | Adds less than 1.0% THD. |
| 3 dB down at 1000 Hertz, 40 dB decade to below 50 dB with resistive load. |
Noise Attenuation |
|
| 120 dB or greater. |
Noise Attenuation |
|
Audible Noise | 45 dB to 55 dB, depending on kVA rating. |
Turn On Characteristics | When energized voltage overshoot will be less than 5% of nominal for 1 cycle |
| or less. |
Overload Rating | 1000% for 1 cycle and 200% for 10 seconds. |
Ambient Rating |
*Optional extended input regulation range provided on some units. If provided, reference description next to the units specification tag. 50 Hz models available.
Listed to UL1012, Standard for “power units other than Class 2”.
1.4.2Main Transformer Specification
Windings | All copper. |
Magnetics | Grain orientated, M6 grade, stress relieved transformer steel is utilized for |
| minimum losses and maximum efficiency. |
Insulation | Class (N) 200 all sizes. |
Shielding | Multiple triple copper shield to minimize interwinding capacitance, transient, |
| and noise coupling between primary and secondary windings. |
Cooling | Convection, operating temp is 130 degrees Celsius maximum rise |
| above ambient. |
Isolation | Output is fully isolated from input. |
Introduction - Specifications | 1 — 3 |