2.P1 will adjust the overvoltage set point. One turn on P1 will change the voltage level approximately 1 volt. Clockwise = Decrease Sensitivity.
3.9.3.3 Delay Adjustment
1.The delay adjustment can be adjusted for a minimum of 5 cycles to a maximum of 15 seconds. The standard set point is 6 seconds.
2.P3 adjusts the delay.
◗All the way
◗All the way clockwise = 15 seconds.
After two turns clockwise from the full
3.10Manual Bypass Switch Option
The manual bypass switch is a break before make switch located on the
NOTE: This switch may be added in the field.
3.10.1 Normal Mode
With the switch in the normal position, the
3.10.2 Bypass Mode
With the switch in the bypass position, the
CAUTION: | PRIOR TO SWITCHING FROM ONE POSITION TO ANOTHER, TURN OFF THE |
| AC INPUT BREAKER. SOME SYSTEMS ARE EQUIPPED WITH |
| SWITCHES. WITH THESE SWITCHES THE SWITCH WILL SHUNT TRIP THE |
| INPUT BREAKER WHEN PRESSED IN. |
|
|
3.10.3 Remote Emergency Power OFF (REPO) (Optional)
The REPO is operated by a remote push button that when depressed will shunt trip the
3 | Maintenance |