Installation and User Manual
Table
Unit Size | Input | Input | Minimum | Maximum |
in kVA | Breaker | Wire | Ground Wire | Output |
| Size | Size | Size | Current |
10 | 15 Amp | #10 | #10 | 28 |
15 | 25 Amp | #10 | #8 | 42 |
25 | 50 Amp | #8 | #4 | 70 |
30 | 50 Amp | #8 | #4 | 83 |
45 | 80 Amp | #6 | #2 | 125 |
50 | 80 Amp | #6 | #2 | 139 |
75 | 125 Amp | #1 | #6 | 208 |
100 | 150 Amp | 1/0 | 4/0 | 278 |
125 | 200 Amp | 1/0 | 2 pcs 1/0 | 347 |
150 | 225 Amp | 1/0 | 2 pcs 2/0 | 417 |
225 | 350 Amp | 4/0 | 2 pcs 250 | 625 |
300 | 500 Amp | 2 pcs 2/0 | 3 pcs 250 | 833 |
Table based on 480 VAC input and 208 VAC output.
Table
Unit Size | Input | Input | Minimum | Maximum | |
in kVA | Breaker | Wire | Ground Wire | Output | |
|
| Size | Size | Size | Current |
10 | 40 Amp | #8 | #10 | 28 | |
15 | 60 Amp | #8 | #8 | 42 | |
25 | 110 Amp | #4 | #4 | 70 | |
30 | 110 Amp | #4 | #4 | 83 | |
45 | 175 Amp | #1 | #2 | 125 | |
50 | 175 Amp | #1 | #2 | 139 | |
75 | 300 Amp | 2/0 | 2/0 | 208 | |
100 | 350 Amp | 4/0 | 4/0 | 278 | |
125 | 450 Amp | 2 pcs 1/0 | 2 pcs 1/0 | 347 | |
150 | 600 Amp | 2 pcs 3/0 | 2 pcs 3/0 | 417 | |
225 | 800 Amp | 2 pcs 250 | 2 pcs 250 | 625 | |
300 | 1200 Amp | 3 pcs 250 | 3 pcs 250 | 833 | |
Table based on 208 VAC input and 208 VAC output. |
|
| |||
|
|
| |||
NOTE: |
| Refer to NEC for output wire size based on output breaker size and Article 310 | |||
|
| Section 8A. |
|
|
|
|
|
|
|
|
|
Installation and Operation | 2 — 7 |