Installation and User Manual
Maintenance
3.0Scope
This section contains preventive maintenance for the
WARNING: | HIGH VOLTAGE DANGER OF ELECTRICAL SHOCK, TURN OFF ALL POWER |
| SUPPLING THIS EQUIPMENT PRIOR TO MAINTENANCE. ONLY QUALIFIED |
| ELECTRICIANS SHOULD PERFORM MAINTENANCE OR TROUBLE SHOOTING. |
|
|
3.1Preventive Maintenance
To ensure longer component life and trouble free operation, minor preventive maintenance procedures should be performed at regular intervals, recommended once every year. More frequent inspection intervals would be needed for more severe operation conditions and and larger number of hours of continuous operation.
At each service inspection, remove any dust, dirt or foreign particles. Thoroughly inspect and tighten any loose electrical connections. A slight tug should be used to test if there are any loose electrical connections. Make sure all cooling fans are running.
A.At each service inspection, remove top and side panels and carefully remove any accumulated dust, dirt, or foreign particles. Special care should be exercised in cleaning the thyristors, heat sinks, and the control assembly.
B.Inverse Parallel Silicon Rectifiers (SCRs) or Thyristors.The silicon controlled rectifiers (SCRs) usually fail in the shorted mode. When this happens, normally the fusible link within the SCR will be blown open to clear the short and prevent damage to the transformers. The individual SCR can be checked with an ohmmeter. Refer to Section 3.4 for resistance checking procedures.
C.A simple performance checklist has been developed for use in maintenance, on pages
D.After items
E.Replace top and side panels. Turn unit on with no load. Check item 9 on the performance checklist.
F.Turn on loads and check itemsNOTE: | Preventive Maintenance plans are available. Please contact the Customer Care |
| Center for information. |
|
|
Maintenance | 3 |