Millennium Enterprises AD-ST1400-25, MLP-A/AR user manual RS-485 Communication, Terminal Board

Models: AD-ST1400-25 MLP-A/AR

1 28
Download 28 pages 42.29 Kb
Page 11
Image 11
(Terminal Board)

Net Safety Monitoring Inc

Figure 5: Wiring—Controller and Sensor

Terminal Board

RST

+24V

COM

RST

 

+24V

 

Power

COM

4-20

Terminals

 

ISO

 

 

 

SENSOR AND CONTROLLER

WARNING:

Power to the unit must be OFF before wiring.

Note: The Sensor may be factory installed to the Controller. If so, you need only connect the Power Terminals.

1.Remove the Controller’s Housing Cover.

2.Connect the Sensor to the Sensor Terminals (if necessary) and the Output Terminals to the output signal wires.

Table 1: Controller/Sensor Connections

 

 

4-20

A

 

ISO

 

 

B

Modbus RTU

Red+

 

 

COM

Terminals

Blk

 

-

to PLC

 

 

 

 

 

Shld

Red

Blk

-Sensor

RS-485 Communication - Terminals

Shld

Sensor Board Terminals

Sensor

 

Controller

Wire

 

(Sensor Board)

 

 

 

Red

=

Red (+24 V)

Black

=

Blk (Sig)

 

 

-

 

 

-

 

 

 

Shield

=

Shld

 

 

 

Terminal Board Power

Controller

 

Power

(Terminal Board)

 

Connections

 

 

 

RST

=

Remote Reset

+24V

=

Power (+)

COM

=

Power (-)

4-20

=

Current Loop

 

 

Output

ISO

=

+24 V isolated

 

 

4-20 power

 

 

 

Sensor Board

Sensor Wires

Note: For Sensor Separation instructions, see Figure 6, "Wiring—Sensor Separation", on page 7.

3.Replace the Controller’s Housing Cover.

4.Turn Controller On.

5.Ensure display reads Start Delay , Status LED is Red Slow Flash and current output displays 3.0 mA. This is the start-up delay sequence which will last approximately 90 seconds.

RS-485 Communication

Connect devices in a chain via the Modbus terminals. The last device in the chain requires end of line termination (refer to "MODBUS Termination" on page 9).

Note: If the 4-20 mA signal is not used, connect a jumper between the 4-20 terminal and the COM terminal on the Terminal Board.

MLP-A/AR/AD-ST1400-25

6

Page 11
Image 11
Millennium Enterprises AD-ST1400-25, MLP-A/AR user manual RS-485 Communication, Terminal Board