Net Safety Monitoring Inc

NON-ISOLATED/ISOLATED WIRING

Terminal Connection

Figure 7: Non-isolated Terminal Connection

Terminal Board

Power Terminal Strip

Current Output

To set an isolated current output, simply move the Jumper (shorting jack) to the isolated current position (refer to Figure 9, "Jumper Positions", on page 8).

Note: Unless otherwise specified, all models ship with non-Isolated current output.

Figure 9: Jumper Positions

RST

+24V

COM

4-20

ISO

to Monitor

Figure 8: Isolated Terminal Connection

Terminal Board

Power Terminal Strip

RST

+24V

COM

4-20

to Monitor

ISO

Power Supply

Power Supply

Terminal Board

Sensor Board

Jumper—Position Jumper (shorting jack) over pins to set power source for current output.

Position 3 & 2 =

Non-isolated (default)

Position 1 & 2 = Isolated

Termination Jumper—Is non- functional in this application and can be placed in any position or removed entirely.

MLP-A/AR/AD-ST1400-25

8

Page 13
Image 13
Millennium Enterprises AD-ST1400-25, MLP-A/AR user manual Terminal Connection, Current Output, NON-ISOLATED/ISOLATED Wiring