Siemens S5-135U/155U appendix Setting and Connecting the Fan Submodule, Step Action

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 138
Image 138

Central Controllers and Expansion Units Power Supply Units

4.5.2Setting and Connecting the Fan Submodule

Before starting up your fan submodule, you must perform certain steps according to your requirements with respect to fan submodule behavior in the event of a fault.

The fan submodule is delivered in the following state:

SFitted in the CC or EU frame you ordered

SAC line voltage set to 230 V

If you wish to retain this setting, you can skip Steps 2 to 5.

Step

1

2

3

4

5

6

Action

 

 

 

Check the setting and cabling

 

 

 

Remove the fan submodule

If required

 

 

Fit the fan submodule

If required

 

 

Wire the fan submodule to the installation (including fitting

 

an isolating device to disconnect the AC line voltage)

 

 

 

On the -3LA11 set the voltage selector switch (factory

If required

setting 230 V)

 

 

 

Switch on the fan submodule for the first time

 

 

 

Establishing the Wiring of the fan submodule must be planned within the scope of wiring the

Wiringentire control system. The information required for the purpose and decision-making aids (for example, for local or central grounding) can be found in Chapter 3, Installation Guidelines.

Establishing the Two relay outputs allow you to install additional external signaling circuits

Signaling Circuits for fault states, for example, to connect a cabinet lamp or horn.

4-72

System Manual

C79000-G8576-C199-06

Page 138
Image 138
Siemens S5-135U/155U appendix Setting and Connecting the Fan Submodule, Step Action