Digital Input/Output Modules

Only the flag word (FW) may be accessed during the cyclic program.

Accessing the I/O bytes in the process image will result in alarm loss. Addressing of the module must therefore be above address 127. Double accessing of I/O bytes, even from different CPUs, is not permissible (alarm loss).

The four I/O bytes of a module must be scanned successively and in ascending order. The scanning of byte n inhibits the input circuit of the module, and the scanning of byte (n + 3) enables them again.

Settings on the

Make the following settings on the module to operate it with a process alarm

Module

via IB 0:

Step

Action

1

2

3

4

Insert jumpers X3 and X4

Set switch row S1 to Off.

Set bit 0 on switch row S2 to On, and all other switches to Off.

Set switch row S3 to choose whether the interrupt is to be initi- ated with a positive-going (leading) or negative-going (trail- ing) edge. The setting of a pair of switches applies to an entire byte.

 

 

S1

 

0

IR-A

 

1

IR-B

 

2

IR-C

 

3

IR-D

 

4

IR-E

 

5

IR-F

:OFF

6

IR-G

:ON

7

INT

 

S2

0

Bit 0

1

Bit 1

2

Bit 2

3

Bit 3

4

Bit 4

5

Bit 5

6

Bit 6

7

Bit 7

 

S3

 

0

}

Byte 3

1

 

 

 

2

}

Byte 2

 

3

 

 

 

4

}

Byte 1

5

 

 

6

}

Byte 0

 

7

 

 

 

Byte 0: Positive-Going Edge

Byte 1: Negative-Going Edge-

Byte 2: Both Edges

Byte 3: No Process Interrupt

Figure 8-5 Switch Settings for Operation with Process Alarm via IB 0 (Example)

System Manual

8-11

C79000-G8576-C199-06

Page 323