Siemens S5-135U/155U appendix Standby Operation

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 226
Image 226

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Standby Operation

In this standby state of the unit

 

S the battery-backed RAM submodule is in the CPU;

 

S the PLC is switched off (Power Off);

 

S the backup battery of the PLC is providing backup of the RAM

 

submodule;

 

S the submodule battery is not supplying power.

 

 

 

Note

 

It is only possible to insert and remove the RAM submodule in this state

 

without data corruption.

 

 

 

If the backup battery in the PLC fails in this state, the submodule battery

 

provides backup of the RAM submodule. This prevents loss of data.

Submodule

In this standby state of the submodule

Standby

S the RAM submodule has been removed from the CPU;

 

 

S the submodule battery is providing backup of the RAM submodule;

 

S the contents of the battery-backed RAM are retained.

Battery Monitoring The battery of the battery-backed RAM submodule is monitored. When the

and Battery Fault RAM submodule goes to normal operation (battery-backed RAM is in the CPU, supply voltage of the PLC is switched on), the battery monitor on the submodule detects the following faults:

SSubmodule battery is not present.

SSubmodule battery is faulty (voltage less than 2.6 V).

The red battery fault LED on the front of the submodule is continuously lit.

Note

A temporary voltage drop of the submodule battery in the standby state, e.g. caused by storage below 0 oC or a battery change, is not detected by the battery monitor if the voltage dip is corrected by plugging in the RAM submodule and switching on the PLC. However, the voltage dip may have led to a loss or corruption of RAM submodule data.

5-86

System Manual

C79000-G8576-C199-06

Page 226
Image 226
Siemens S5-135U/155U appendix Standby Operation