Analog Input/Output Modules

9.5.13Technical Specifications

6ES5 465-4UA12 Analog Input Module

Rated input ranges with cards for every 4 channels

±6ES5 498-1AA11

±6ES5 498-1AA21

±6ES5 498-1AA31

±6ES5 498-1AA41

±6ES5 498-1AA51

±6ES5 498-1AA61

±6ES5 498-1AA71

Number of inputs

Measured-valuerepresentation

$50 mV/$500 mV/Pt 100

$1 V

$10 V

$20 mA

4 to 20 mA for two-wire transducer

$5 V

4 to 20 mA for four-wire transducer

16 voltage/current inputs or

8 resistance inputs (Pt 100)

13 bits (two's complement) or 12 bits + sign;

$2048 units in rated range;

512 to 2560 units for 4 to 20 mA

Measuring principle

Isolation

Permissible potential difference between reference potentials of sensors and the module (UCM) and between sensors (chan- nels)

Power Supply

±digital section from system bus

±analog section from load voltage

±enabling for module F+/F-

±tripping current L+

Constant current source for Pt 100 connection IC+/IC-

Integration time

Encoding time per measured value

Cycle time for 8 measured values with 2048 units (max. delay time for measured-value acquisition)

Input resistance (with card) for input ranges: $50 mV/$500 mV/Pt 100

$1 V

$5 V/$10 V $20 mA

4 to 20 mA

Integrating

No

$1 V max.

5 V $ 5 %; 150 mA typical

24 V

24 V; approx. 5 mA

24 V; approx. 5 mA

2.5 mA; TC = $ 5 x 10±5/K

20 ms at 50 Hz; 16 2/3 ms at 60 Hz

60 ms at 50 Hz; 50 ms at 60 Hz

Approx. 0.48 s at 50 Hz

Approx. 0.48 s at 50 Hz

w10 MW

90 kW

50 kW

25 W

31.25 W

9-72

System Manual

C79000-G8576-C199-06

Page 454
Image 454
Siemens S5-135U/155U appendix Technical Specifications, 6ES5 465-4UA12 Analog Input Module