8.4.166ES5 457-4UA12 Digital Output Module

Rated supply voltage L+

Number of outputs (decoupled via diodes)

Isolation

Range for supply voltage

Fusing

Output voltage

for logic 1:

(L+)-Switch

 

 

 

(L±)-Switch

 

for logic 0:

(L+)-Switch

 

 

 

(L±)-Switch

 

Switching current (resistive, inductive load)

 

 

 

Residual current at logic 0

 

 

 

 

 

Switching current for lamps

 

 

 

 

Switching frequency

with resistive load

 

 

with inductive load

 

 

 

 

Breaking voltage (inductive)

Coincidence factor (total load capability) ventilated

not ventilated

Permissible line length

24 to 60 V DC

16, short-circuit protected 1)

Yes, 16 outputs

20 to 72 V DC

16 x 1 A, slow

L+ ± 2.5 V min.

2.5V max.

3 V max.

L+ ± 3 V min.

5 mA to 0.5 A 2)

1 mA max.

0.22 A max. (5 W)

100 Hz max.

2 Hz max. at 0.5 A

Limited to L+ ± 75 V 3)

100 %

50 %; 100 % up to 35 oC

400 m max. unshielded

Power supply

Digital section from system bus

Power dissipation (rated operation)

Enable input (F+/F±)

5 V, 120 mA typical

13.0 W

Rated input voltage

Input voltage

for logic 1

 

for logic 0

 

 

Rated input current

at 24 V DC

 

at 48 V DC

 

at 60 V DC

 

 

Permissible line length

 

 

 

24 to 60 V DC

13 to 72 V

± 72 to 8 V

2.5mA

5 mA

6.5mA

200 m max.

Short-circuit monitoring

Indicator for signaling output (H+, H±)

Output voltage as L+ switch for logic 1 for logic 0

Switching current

Voltage test to VDE 0160

Red LED for 16 outputs

L+ ± 5 V min. 3 V max.

10 mA max., short-circuit protected

Between two groups: 1250 V AC;

Between group and ground point: 1250 V AC

Mechanicalspecifications

Dimensions (W x H x D)

Weight

40 mm x 255 mm x 195 mm

Approx. 0.6 kg

1)Short-circuit protection responds with line resistance 9 ohms at 24 V DC, 30 ohms at 60 V DC.

2)One digital input is permissible as minimum load.

3)At L+ voltages of more than 72 V, the logic 0 of the output can rise to 13 V. A digital input follower will interpret this signal as a logic 1 (possible fault).

8-62

System Manual

C79000-G8576-C199-06

Page 374
Image 374