Siemens S5-135U/155U appendix Connecting Cable for Point-to-Point Communication

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 261
Image 261

CPUs, Memory Cards, Memory Submodules, Interface Submodules

Connecting Cable for Point-to-Point Communication

If the CPU communicates as master in a point-to-point link with a slave, a connecting cable can be used instead of the bus terminal.

Shown in the following figure is connecting cable for point-to-point communication from the SINEC L1 submodule in the CPU to a partner.

Connecting cable: CPU - partner (point-to-point communication)

CPU 928B

 

 

 

e.g. CPU 928B, 941...945

 

 

 

 

CPU 102, 103, AG 90U/95U

 

9

+ RxD

± TxD

7

Receiver

 

 

 

Transmitter

 

2

± RxD

+ TxD

6

 

15

M

+ 20 mA

11

 

11

+ 20 mA

M

+ 24V

+ 24V

15

 

6

+ TxD

± RxD

2

Transmitter

7

± TxD

+ RxD

Receiver

 

9

Housing, GND

1

Shield

 

1

 

 

 

Housing, GND

Figure 5-30 SINEC L1 Submodule: Connecting Cable for Point-to-Point Communication via the SINEC L1 Submodule

System Manual

5-121

C79000-G8576-C199-06

Page 261
Image 261
Siemens S5-135U/155U appendix Connecting Cable for Point-to-Point Communication, CPU 928B CPU 102, 103, AG 90U/95U