Installation Guidelines

Operating a

In cases in which the higher-level power supply is not grounded, you must

Programmable

connect the programmable controller to a separate protective

Controller with

conductor/ground (e.g. foundation ground). Operation of the PLC with

Process I/Os from

non-floating power supplies is not allowed.

an Ungrounded

When connecting the power supplies, please note:

Supply

 

 

 

 

In 3 x 230 V systems, you may connect the power supply directly to two

 

 

 

 

 

 

 

 

 

 

 

 

 

 

phases.

 

 

 

 

 

 

 

 

 

 

 

 

 

Low-Voltage Distribution,

L1

 

 

 

e.g. IT System (3 X 230V)

 

L2

 

 

 

 

 

 

 

L3

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

À

 

Schrank

 

 

Programmable Controller

 

 

 

 

Control Power Supply

 

 

 

 

 

 

AC

L+

L+/L1

 

 

 

 

 

DC

 

Uint

CPU

 

 

 

 

 

 

 

 

 

L1

L±/L2

 

 

 

 

 

PS 0 V

 

 

 

 

 

L2

 

Non-Float-

Non-Float-

Floating

Floating

 

 

PE

 

ing Input

ing Output

Input

Output

 

PE

 

Protective Conductor Bar

Protective

in Cabinet

Conductor

 

Grounding

 

￿

￿

AC

Process I/Os

AC

 

￿24 to 230 V AC Load Supply for AC Modules

￿

￿

￿

 

 

 

AC

DC

￿ ￿

AC

DC

5 to 60 V DC Load Supply for Non-Floating DC Modules

￿

5 to 60 V DC Load Supply for Floating DC Modules

Figure 3-10 Operating a Programmable Controller with Process I/Os from an Ungrounded Supply

In 3 x 400 V systems, a connection between phase and neutral conductor is not allowed (excessively high voltage in the event of a ground fault). Intermediate transformers should be used in these systems.