Analog Input/Output Modules

Addressing for

However, analog input modules and analog output modules may be given the

Cyclic/Selective

same address with cyclic sampling because they are distinguished by the user

Sampling

program. This is not possible with selective sampling.

 

For cyclic sampling, you can address the module in the address range from 0

 

to 255, and for selective sampling from 128 to 255. For selective sampling,

 

you can also use the address range from 0 to 127 after appropriate

 

programming in DB 1 of the user program.

 

Example:

 

On an analog output module with 8 outputs with start address 144 (IB 144 =

 

output byte 144), output channel 7 is to be scanned by the program.

Step

1

2

3

Action

Affix the self-adhesive label with address 160 on the free field under the addressing switch on the module. ADB 4 and ADB 7 are marked on the label.

Press the appropriate rockers of the addressing switch down on the side marked by a dot on the module cover. Set the other rockers to the opposite setting. This sets the start address of the module.

ADB 4 and ADB 7 results in 24 + 27 = 16 + 128 = 144

Enter the address 144 + 7 x 2 = 158 in the program for input channel 7.