8.4.156ES5 456-4UB12 Digital Output Module

Rated supply voltage L

Number of outputs

Isolation

Range for supply voltage

Fusing

Output voltage

for logic 1 for logic 0

Residual current at logic 0

Switching current (resistive, inductive load) ventilated

not ventilated

Switching current for lamps ventilated

not ventilated

Contactor size

Max. inrush current for

3 ms

20 ms

50 ms

Switching capacity per module for UL

for CSA

Permissible line length

115 to 230 V AC (47 to 63 Hz)

8, conditional short-circuit protection 1)

Yes, 8 outputs

88 to 264 V AC

3.5 A fast; 1 fuse per output

L± 1.5 V min. 30 V max.

5 mA max.

40 mA to 2 A; 2)

40 mA to 1 A; 2)

40 mA to 2 A;

40 mA to 1 A;

0 (Type 3TB40) to 14 (Type 3TB58) at 230 V AC; 00 (Type 3TJ ..) to 8 (Type 3TB52) at 115 V AC;

16A

8A

6.5 A

1440 VA max.

2000 VA max.

300 m max. unshielded

Power supply

Digital section from system bus

Power dissipation (rated operation)

Enable input (F+/F±)

Voltage test to VDE 0160

5 V, 100 mA typical

18.0 W

Jumper in front connector

Between two groups: 2000 V AC

Between group and ground point: 1500 V AC

Mechanicalspecifications

Dimensions (W x H x D)

Weight

40 mm x 255 mm x 195 mm

Approx. 0.6 kg

1)Protected by a fuse.

2)Contactors of Series 3TJ can only be operated at 115 V AC.

8-60