Siemens S5-135U/155U appendix Examples for Determining the Type of Cabinet, Cabinet Design

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 64
Image 64

Installation Guidelines

!

Caution

Modules with a hard disk drive can only be used at an ambient temperature of up to 50 °C.

3.7.4Examples for Determining the Type of Cabinet

The following example shows the maximum permissible ambient temperature with various cabinet types and the same power dissipation.

Example

The following equipment configuration is given:

1

Central controller

200 W

2

Expansion units, 250 W power dissipation each

500 W

1

Load PS, 24 V/40 A, 6EV1 362-5BK00 (full load)

200 W

 

 

 

 

Total power disspation

900 W

From Figure 3-16, with a total power dissipation of 900 W, the maximum ambient temperatures given by the table are as follows:

Cabinet Design

Closed, with natural convection and forced circulation (Curve 3)

Open with through-ventilation (Curve 2)

Closed, with heat exchanger (Curve 1)

Max. Permissible Ambient Temperature

(Operation not possible)

Approx. 33 °C

Approx. 42 °C

3-38

System Manual

C79000-G8576-C199-06

Page 64
Image 64
Siemens S5-135U/155U Examples for Determining the Type of Cabinet, Cabinet Design, Max. Permissible Ambient Temperature