Analog Input/Output Modules

Cycle time for 8 measured values with 2048 units (max. delay time for measured-value acquisition)

Input resistance (with card) for input ranges: $12.5 mV/$50 mV/$500 mV/Pt 100 $1 V

$5 V/$10 V $5 V/$20 mA 4 to 20 mA

Measuring point-related error signal

±for overflow

±for broken wire

Max. permissible input voltage without destruction

Interference suppression for f = n x (50/60 Hz $1 %)

±with common-mode interference

±with differential-modeinterference

Error referred to rated value

±linearity

±tolerance

at w50 mV at $ 12.5 mV

±polarity reversal error at w 50 mV

at $12.5 mV

±temperature error

Error caused by modules with input range

$1 V/$ 5 V /$ 10 V

$20 mA/4 to 20 mA

Voltage test to VDE 0160

Surge voltage test to IEC 255-4

Extended Pt 100 measuring range

Measuring range including overrange

Resolution

Basic error at T = 25 oC

Operational error at T = 0 to 65 oC

Range card

Environmentalspecifications

Approx. 0.48 s at 50 Hz

w10 MW

90 kW

50 kW

25 W

31.25 W

Yes

Yes, configurable

(at $12.5 mV, $ 50 mV $ 500 mV and Pt 100 1) )

$18 V; 75 V for 1 ms max. and duty ratio 1:20

w100 dB

w40 dB, interference voltage amplitude

but 100 % max. of measuring range referred to peak value

$1 unit

$1 unit

$3 units

$1 unit

$2 units

1 x 10 ±4 /K

2 x 10 ±3; TC = $ 10 x 10 ±5 /K 10 ±3; TC = $ 5 x 10 ±5 /K

Between inputs and ground point tested at 500 V AC

Between inputs and L-:

Vp = 1 kV, 1.2/50 s

Approx. - 100 oC to + 100 oC 0.025 oC per unit

$0.2 oC max. $0.5 oC max. 6ES5 498-1AA11

See technical specifications of the S5-135U/155U CC

1)In the event of open-circuit of the live IC+ and IC- lines, the digital value 0 is indicated.

9-30

System Manual

C79000-G8576-C199-06

Page 412
Image 412
Siemens S5-135U/155U appendix Analog Input/Output Modules