Analog Input/Output Modules

9.3.11Connecting Resistance Thermometers in the Extended Pt 100 Range

The series-connected resistance thermometers (up to 8 Pt 100s) are fed with a current of 2.5 mA (IC+/IC-) by a constant current generator. The voltage at the Pt 100s is picked off at measurement inputs M+ and M-.

In this mode, the temperature range of approximately -100 °C to +100 °C has a more accurate resolution. The mode is printed on the cover of the module as follows: ªresistance thermometer compensated low range.ºYou should only use the 6ES5 498-1AA11 range card (" 50 mV / 500 mV).

Unused inputs must be connected in parallel to a wired input. In the following figure, for example, these are the inputs CH4 to CH7.

 

M+

 

 

Ch0

6ES5498-

 

1AA11

 

M+

 

 

Ch1

 

 

 

 

M+

 

 

Ch2

 

 

 

 

M+

 

 

Ch3

 

 

 

 

M+

6ES5498-

 

Ch4

 

1AA11

 

 

 

 

M+

 

 

Ch5

 

 

 

 

M+

 

 

Ch6

 

 

 

 

M+

 

 

Ch7

 

 

 

 

Ic±

 

 

Ic+

 

24V

L+

2.5mA

 

M24V

 

 

 

Figure 9-10 Connecting Resistance Thermometers in the Extended Pt 100 Range

System Manual

9-21

C79000-G8576-C199-06