Siemens S5-135U/155U Case of a fault, the red LED ªFan Faultº lights up, Terminals Cabling

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 139
Image 139

Central Controllers and Expansion Units Power Supply Units

Selecting Cables The following applies to selecting the cables for the terminals:

Terminals

 

Cabling

 

 

 

 

 

Power supply AC line

Phase

L 1

 

 

Neutral

N

 

 

 

 

Protective conductor

 

 

 

 

 

 

 

Relay terminals, also suitable

 

 

 

to 230 V AC / 3 A

 

 

 

 

 

 

 

Max. Permissible Cable

Cross-Sections

4 mm2 solid or 2.5 mm2 flexible

4 mm2 solid or 2.5 mm2 flexible

4 mm2 solid or 2.5 mm2 flexible

4 mm2 solid or 2.5 mm2 flexible

Installing and

Removing the Fan

Submodule

Wiring up the Fan Submodule

Switching on the Fan Submodule for the First Time

!

Fault Indications/ Fault Diagnostics

For installing and removing the fan submodule, refer to the instructions in Section 4.3.2 on the power supply unit. These also apply in principle here.

FFor wiring up the fan submodule, refer to the instructions in Section 4.3.2 on the power supply unit. These also apply in principle here.

The fan submodule is switched on when the line voltage for the central controller or expansion unit is switched on.

Caution

If you have set the voltage selector switch on the -3LA11 to 120 V, but the actual voltage value is 230 V, the fan submodule may be damaged when line voltage is switched on.

Fan submodule faults are indicated via relay contacts (ªMonitor Outputº) and an LED.

The following table shows when the relay contacts are open or closed:

Fan Submodule

Relay Contact 1-2

Relay contact 2-3

 

 

 

Switched off

open

closed

 

 

 

In normal operation

closed

open

 

 

 

During fault

open

closed

 

 

 

In the case of a fault, the red LED ªFan Faultº lights up.

System Manual

4-73

C79000-G8576-C199-06

Page 139
Image 139
Siemens S5-135U/155U appendix Case of a fault, the red LED ªFan Faultº lights up, Terminals Cabling