Central Controllers and Expansion Units Power Supply Units

4.1.5Technical Specifications

Important for the USA and Canada

The following approvals have been granted for the central controllers and expansion units:

SUL Listing Mark

Underwriters Laboratories (UL) to Standard UL 508, Report E85972

SCSA Certification Mark

Canadian Standards Association (CSA) to Standard C 22.2 No. 142, Report LR 63533C

Unit safety

 

 

 

The unit complies with:

VDE 0160, IEC 1131-2

Protection against overvoltage

 

 

Overvoltage Class 2 (not with PS -3NA12)

VDE 0160 A1

 

 

Class of protection

I

 

 

Type of protection

IP 20 to IEC 529/DIN 40050

(when empty slots are covered by dummy front plates)

 

 

 

Climatic ambient conditions (tested to DIN IEC 68-2/-1/2/3)

 

 

 

Ambient temperature in operation

0 to 55 °C

(supply air measured at lower air inlet of the unit)

 

 

 

Transportation and storage temperature

Temperaturevariation:

in operation

during transportation and storage

(when delivered at less than 0 oC, at least 3 h

acclimatization because of possible

condensation)

- 40 to 70 °C

10 K/h max.

20 K/h max.

Relative humidity:

in operation, during transportation and

storage

Altitude:

in operation

during transportation and storage

95% max. at 25 °C, no condensation

-1000 m to + 1500 m above sea level

(1080 hPa to 860 hPa)

-1000 m bis + 3500 m above sea level

(1080 hPa to 660 hPa)

Pollutants:

0,5 cm 3 / m 3, 4 days

SO2

H S

0,1 cm 3 / m 3, 4 days

2

 

Mechanical ambient conditions (tested to DIN IEC 68-2-6)

 

 

 

Vibration during operation

10 to58 Hz (const. amplitude 0.075 mm)

 

58 to 500 HZ (const. acceleration 1g)

 

 

System Manual

4-13

C79000-G8576-C199-06

Page 79
Image 79
Siemens S5-135U/155U appendix Technical Specifications, Important for the USA and Canada, Unit safety