CPUs, Memory Cards, Memory Submodules, Interface Submodules

Startup

The modules must be inserted at the correct slots in the central controller.

 

The backup battery must be fitted and in order for the CPU to start.

Overall Reset

Proceed as follows:

Step

1

2

Action

Set the mode switch to STOP.

Switch the system voltage on.

Resultat

The following LEDs must light up on the CPU:

±Red STOP LED (flashing rapidly)

±Red INIT LED, briefly

±Red BASP 2) LED

3

Hold the MC 1) switch in the OVERALL RESET setting and simultaneously set the mode switch from STOP to RUN.

Die rote LED ªSTOPº zeigt nun Dauerlicht.

1)MC: Momentary-contact

2)BASP: Command output inhibit

If the red SYS FAULT LED also lights up, an error has occurred during overall reset. In this case the measures described must be repeated. If necessary, switch the system voltage off and on again.

If the LED is still lit, the module is faulty.

Reset

Continue as follows:

 

 

 

 

Step

Action

 

 

 

Result

4

5

Set the mode switch to STOP.

Hold the MC switch in the RESET setting and simultaneously set the mode switch from STOP to RUN.

±Red STOP LED goes off

±Green RUN LED lights up

±Red BASP LED goes off

The CPU is now in the RUN state but still has no user program.

System Manual

5-25

C79000-G8576-C199-06

Page 165
Image 165
Siemens S5-135U/155U appendix Set the mode switch to Stop Switch the system voltage on, Resultat