Monitoring Module

10.3.1Addressing

Example 1

S5-130K, S5-135U or S5-155U

 

 

 

 

 

 

 

 

1st MM

 

 

 

2nd MM

 

 

3rd MM in the

 

 

 

 

 

 

 

 

 

 

 

last EU

 

 

S1

e.g.

127

(7FH)

3)

e.g.

126

(7EH)

3)

85

(55H)

4)

 

S2

e.g.

127

(7FH)

3)

e.g.

126

(7EH)

3)

170

(AAH)

4)

 

S3

 

85

(55H)

5)

 

85

(55H)

5)

85

(55H)

5)

 

S4

 

170

(AAH)

5)

 

170

(AAH)

5)

170

(AAH)

5)

User program in OB 1 or FB 0

 

 

without S5-DOS

with S5-DOS

 

L

EB

127

L

PY

127

T

AB

127

T

PY

127

L

EB

126

L

PY

126

T

AB

126

T

PY

126

L

EB

85

L

PY

85

T

PB

170

T

PY

170

BE

 

 

BE

 

 

3)Possible addresses 0 (00H) to 255 (FFH)

4)To achieve optimum fault detection, set the inverse addresses 85 (55H) and 170 (AAH) at S1 and S2.

5)Since the addresses of the monitoring module switches S3 and S4 are not acknowledged, this must be done by the monitoring module contained in the last expansion unit (the most remote from the central controller). The addresses 85 (55H) or 170 (AAH) of this monitoring module must be coded at switches S1 or S2, respectively.

These addresses may no longer be occupied for I/O tasks.

10-10

System Manual

C79000-G8576-C199-06