Analog Input/Output Modules

If you have preset measurement with respect to ground on switch S9, four channel groups of four channels each are available. You can configure each channel group separately for current or voltage measurement.

This is set with switches S5, S6, S7 and S8. Switches S5 and S7 allow three settings (left, midpoint and right); switches S6 and S8 allow two settings (left and right). The switch settings relate to the locations on the module shown in Figure 9-26:

Setting the current/voltage measurement for channel group I

Channel Group I (Channels 0 to 3)

Current

Switch S5

Voltage

Setting the current/voltage measurement for channel group II

Channel Group II (Channels 4 to 7)

Current

Switch S7

Voltage

Setting the current/voltage measurement for channel group III

Channel Group III (Channels 8 to 11)

Current

Switch S6

Voltage

Setting the current/voltage measurement for channel group IV

Channel Group IV (Channels 12 to 15)

Current

Switch S8

Voltage