Siemens S5-135U/155U appendix Monitoring for continuous bus assignment

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 282
Image 282

Multiprocessor Operation/Coordinators

Bus Enable for:

CPU1

2s

CPU2

CPU3

2s +

Bus Lock

CPU4

Bus Lock

Reset

CPUs in Operation

Time

Figure 6-7 Timing Sequences of the Bus Control Signals

Monitoring for continuous bus assignment

The bus lock signal can only be emitted by the CPU which has already received a bus enable signal from the COR 923C. The bus enable time is extended by the duration of the bus lock signal for the CPU (see Figure 6-7). The factory setting for monitoring of the bus lock signal is 2 ms. If the signal remains active for a longer duration, the COR 923C emits a signal which results in a Stop of all CPUs.

The CPU which emitted the bus lock signal for too long a duration, is marked by the CPU in a readable register under address FEFFH (fault register, see Figure 6-8). The assigned BUS FAULT LED in the front plate of the COR 923C lights up. The register is cleared and the LED goes off again when the signal which led to the Stop state becomes inactive.

Communication memory

The communication memory comprises a central battery-backed RAM in the PLC. It has three areas: 1) the communication flags (256 bytes), 2) the semaphores (32), and 3) four memory pages.

The communication flags are located in memory area F200H to F2FFH. The communication flags enable the cyclic interchange of small volumes of data between the CPUs in the S5-135U/155U PLC. The four memory pages serve for the exchange of data blocks between CPUs.

Please consult the Programming Guides of the CPUs to program these two functions.

6-20

System Manual

C79000-G8576-C199-06

Page 282
Image 282
Siemens S5-135U/155U appendix Monitoring for continuous bus assignment, Timing Sequences of the Bus Control Signals