Analog Input/Output Modules

9.7.7 Connecting the Signal Lines

For connection of the signal lines, front connectors for 20 and 40 mm mounting width with crimp connection and 40 mm mounting width with screw connection are available (screwdriver blade width: 3.5 mm, maximum torque: 0.8 Nm).

Use stranded conductor to facilitate handling of the front connector. Ferrules are not required for screw connections, because the screw terminals are provided with wire protection.

When the crimp contact is inserted in the plastic body of the front connector, a click can clearly be heard. This indicates that the contact is engaged. For jumpering or to correct the wiring, you can remove the contacts with a releasing tool (see ordering information) without having to pull out the front connector.

Ferrules are not required for screw connections, because the screw terminals are provided with wire protection. You can use ferrules of 7 mm in length to DIN 46228. The maximum terminal area is 2 x 2.5 mm2.

Terminal

Connector

 

Type

Type

 

 

 

6ES 497-

 

 

 

 

Crimp con-

-4UA12 2)

 

nection

 

 

 

 

 

 

-4UA22 2)

 

Screw con-

-4UB12

 

nection

 

 

-4UB31

 

 

 

 

 

 

Max.

Cross-Section

 

No. of

 

 

Signal or Supply

Aux. Jumper

Contacts

Conductor

in Connector

 

 

1)

 

 

 

42

0.5 mm 2

0.5 mm 2

 

 

 

42

0.5 mm 2

0.5 mm 2

42

0.5 to 2.5 mm 2

0.5 to 1.0 mm 2

42

0.5 to 1.5 mm 2

0.5 to 1.0 mm 2

Connector for

Mounting Width of

Rated Voltage

Module

 

 

 

 

 

5 to 60 V DC

20 mm Operation

 

 

with fan

 

 

 

5 to 60 V DC

40 mm

 

 

 

Operation

5 to 60 V DC

40 mm

without fan

 

 

5 to 60 V DC

20 mm

 

 

 

 

1)To multiply the supply and 0 V ground terminals, and to connect the enable input

2)The crimp contacts must be ordered separately for these types of connector.

!

Caution

Only extra-low voltage 60 V DC with safety separation from system voltage may be used for the 24 V DC supply and for the 24 V DC input signals. Safety separation can be implemented to the requirements of, amongst other sources, VDE 0100 Part 410/HD 384-4-41/IEC 364-4-41 (as functional extra-low voltage with safety separation) or VDE 0805/EN 60950/IEC 950 (as safety extra-low voltage SELV) or VDE 0106 Part 101.

9-108

System Manual

C79000-G8576-C199-06

Page 490
Image 490
Siemens S5-135U/155U appendix Connecting the Signal Lines