CPUs, Memory Cards, Memory Submodules, Interface Submodules

ADF LED

on

The user program has referenced an I/O address in the process image under which no module is inserted.

ZYK LED

on

The maximum cycle monitoring time has been exceeded.

BASP LED

on

Command output is inhibited and the digital outputs will be directly switched to the safe state.

A detailed description of interrupt and error handling can be found in the CPU 928B Programming Guide.

LED SI1

on

on

off

off

LED SI2

Cause

 

 

on

No communication possible at both interfaces.

 

Internal error.

 

 

off

SI1:

 

No communication possible. Internal error.

 

SI2:

 

If used, interface is initialized and ready.

 

 

on

SI1:

 

Interface is initialized and ready.

 

SI2:

 

No communication possible.

 

Wrong interface submodule inserted or wrong

 

parameters for interface or internal error.

 

 

off

First interface and, if used, second interface are

 

initialized and ready.

 

 

5-50

System Manual

C79000-G8576-C199-06

Page 190
Image 190