Digital Input/Output Modules

8.2Installation and Startup

This section describes how to prepare digital input/output modules for installation, and how to install and wire them.

8.2.1Setting the Module Address

 

You set the module address on the addressing switch. This also establishes

 

the necessary assignments between user program and process connection.

 

The address of the digital input modules (input bytes IB 0 to 255 or 252 for

 

the DI/DQ 482) and digital output modules (output bytes QB 0 to 255 or 252

 

for the DI/DQ 482) is the sum of the binary significances established by

 

depressing the individual rockers in the On setting (l).

 

The modules are addressed by the STEP 5 program under their parameters

 

(byte address).

Labeling Field

You can affix the adhesive label with the desired module address on a

 

labeling field under the addressing switch. Suitable labels are supplied with

 

the CC.

 

The switch rockers with which the module address (IB n or QB n) is

 

specified as a decimal number, are marked by dots on the label.

 

Do not use a pencil to set the addressing switch.