Siemens S5-135U/155U appendix Channel number, Module, is given by

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 422
Image 422

Analog Input/Output Modules

Press the individual rockers of the addressing switch downwards with a ballpoint pen or similar object, but not a pencil.

On Setting

 

(Switch Pressed)

Addressing Switch

Adresse (dezimal)

128

64

32

16

8

4

2

1

ADB7

ADB6

ADB5

ADB4

ADB3

ADB2

ADB1

ADB0

ADB0 and ADB1 are not assigned

ADB2 is not connected

Figure 9-14 Labeling of the Addressing Switch

Free Field for Label with Module Address and marked Switch Settings

Decimal Significance of

the Address Bit

Address Bit

 

The address under which the module is referenced by the STEP 5 program is

 

independent of the slot.

Start Address,

For analog input and analog output modules (4 inputs) only the lowest

Subaddress

address (start address) is set. Other addresses (subaddresses) are decoded on

 

the module.

 

 

 

Note

 

The start address of the analog module must be a multiple of the double

 

channel number.

 

4 channels : 0, 8, 16, 24, ... 248

 

 

 

If one of the inputs or outputs (Channel 0 to 3) of a module is to be

 

addressed, the relevant subaddress must be specified in the program.

 

The subaddress of the input or output, based on the start address of the

 

module, is given by:

 

Start address + 2 x channel no. = subaddress

9-40

System Manual

C79000-G8576-C199-06

Page 422
Image 422
Siemens S5-135U/155U appendix Channel number, Module, is given by