Siemens S5-135U/155U appendix Standard Connect- ing Cables of the V.24 Submodule

Models: S5-135U/155U

1 560
Download 560 pages 1.68 Kb
Page 242
Image 242

CPUs, Memory Cards, Memory Submodules, Interface Submodules

With jumper J6, you can set all V.24 receivers so that you only require positive-going signals (positive voltage region).

1

2

3

J6

 

All received signals must be at

 

 

V.24 signal level.

 

 

All received signals can be in the

 

 

positive voltage region.

With the submodule 0AA23, bridge 6 has no function; all signals can lie in the positive range (corresponds to bridge setting 2-3).

With jumper J9, CTS can be set permanently to quiescent potential, i.e. switched through from the front connector.

J9

1 2 3

CTS at quiescent potential CTS at pin 5

Standard Connect- ing Cables of the V.24 Submodule

Standard cables for connecting the V.24 submodule of the CPU to the partner station are available from Siemens in various lengths, up to16 m.

Order numbers and lengths can be found in the ordering information.

Connecting cable for CPU, CP 524, CP 525, CP 544

CPU, CP524/525, CP544

 

 

CPU, CP524/525, CP544

Receiver

 

 

Transmitter

3

RxD

TxD

2

Transmitter

TxD

 

Receiver

2

RxD

3

7

 

 

7

1

Shield

 

1

Housing, GND

 

 

Housing, GND

Figure 5-16 V.24 Submodule: Connecting Cable for CPU, CP 524, CP 525, CP 544

5-102

System Manual

C79000-G8576-C199-06

Page 242
Image 242