Analog Input/Output Modules

9.3.15Technical Specifications

6ES5 460-4UA13 Analog Input Module

Rated input ranges with cards for every 4 channels

±6ES5 498-1AA11

±6ES5 498-1AA21

±6ES5 498-1AA31

±6ES5 498-1AA41

±6ES5 498-1AA51

±6ES5 498-1AA61

±6ES5 498-1AA71

Number of inputs

Measured-valuerepresentation

$12.5 mV/$50 mV/$500 mV/Pt 100

$1 V

$10 V

$5 mA/$ 20 mA

4 to 20 mA for two-wire transducer

$5 V

4 to 20 mA for four-wire transducer

8 voltage/current inputs or

8 resistance inputs (Pt 100)

13 bits (two's complement) or 12 bits + sign;

$2048 units in rated range;

512 to 2560 units for 4 to 20 mA

Measuring principle

Isolation

Integrating

Yes

8 inputs tested with respect to 0 V at 500 V AC

Permissible potential difference between reference potentials of sensors and the module (UCM) and between sensors (chan- nels)

Power Supply

±digital section from system bus

±analog section from load voltage

±enabling for module F+/F-

±tripping current L+

Constant current source for Pt 100 connection IC+/IC-

Integration time

Encoding time per measured value

25 V AC/60 V DC max.

5 V $ 5 %; 130 mA typical

24 V; approx. 50 mA 1)

24 V; approx. 5 mA

24 V; approx. 5 mA

2.5 mA; TC = $ 5 x 10±5/K

20 ms at 50 Hz; 16 2/3 ms at 60 Hz

60 ms at 50 Hz; 50 ms at 60 Hz

1)Plus 20 mA max. per connected two-wire transducer.